How to Do Commercial Electrical Load Calculations

Learn step-by-step how to perform commercial electrical load calculations, ensuring safety and efficiency in electrical systems.


Commercial electrical load calculations are crucial for ensuring the safe and efficient operation of electrical systems in commercial buildings. These calculations determine the total electrical load that the system will support, guiding the design, installation, and maintenance of electrical infrastructure. In commercial environments, the load calculations are more complex than residential settings due to the higher power demands, a variety of equipment, and multiple safety standards that must be adhered to.

In this article, we will delve into the step-by-step process of performing accurate commercial electrical load calculations, incorporating detailed technical terms and methodologies that are commonly used by professionals in the electrical engineering field.

Understanding the Importance of Electrical Load Calculations

Before diving into the process, it's essential to understand why electrical load calculations are necessary. These calculations:

  • Ensure that the electrical system has sufficient capacity to handle peak loads.
  • Prevent overloading circuits, which can lead to tripped breakers, overheating, and potential fires.
  • Comply with local electrical codes, such as the National Electrical Code (NEC) in the U.S., which mandates adherence to specific standards.
  • Optimize energy consumption and improve the overall efficiency of the electrical system.

Key Terms and Concepts

To perform commercial electrical load calculations, it's crucial to be familiar with a few key concepts:

  • Load Factor: This is the ratio of the average load over a given period to the maximum load during the same period. It helps determine how efficiently electrical power is being used.
  • Demand Load: The maximum electrical power that a building or equipment requires at a particular time.
  • Connected Load: The sum of the continuous power ratings of all electrical equipment that will be connected to the electrical system.
  • Diversity Factor: A factor applied to the connected load to account for the likelihood that not all connected devices will operate simultaneously at their maximum rated power.
  • Power Factor (PF): The ratio of real power (measured in kilowatts) to apparent power (measured in kilovolt-amperes). Commercial electrical systems often require power factor correction to reduce energy losses.

Step 1: Gather Information on Electrical Loads

The first step in commercial electrical load calculations is to gather information on all the electrical equipment that will be installed. This includes lighting systems, HVAC (Heating, Ventilation, and Air Conditioning) systems, motors, outlets, and any other electrical appliances.

  • Lighting: Calculate the wattage of all lighting fixtures. Lighting loads are typically calculated based on square footage, with the NEC providing specific requirements for different types of spaces.
  • HVAC Systems: These systems can account for a significant portion of the electrical load. The power requirements are typically found on the nameplates of the HVAC units, measured in kilowatts (kW) or British thermal units per hour (BTU/h).
  • Motors and Machinery: Determine the power requirements for any motors, such as those found in elevators, pumps, or manufacturing equipment. The NEC provides guidelines for motor loads, including considerations for starting currents and running conditions.

Step 2: Apply Load Factors and Demand Factors

Once the connected loads are identified, load factors and demand factors must be applied to calculate the actual load. The NEC provides guidelines for applying these factors based on the type of occupancy (e.g., office buildings, warehouses, restaurants) and the specific equipment.

Lighting Load Calculations

Lighting loads are typically calculated using a load factor based on the type of lighting and occupancy. For instance, office buildings require around 1.3 to 2 watts per square foot, while restaurants may require up to 3 watts per square foot.

The NEC requires that commercial lighting systems use a demand factor of 125% for continuous loads. Continuous loads are defined as those expected to run for three hours or more. This means that for lighting circuits, the load calculation should be increased by 25% to account for this continuous operation.

Receptacle Load Calculations

Receptacles, or general-use outlets, are calculated based on the square footage of the building. The NEC recommends 1 VA (volt-ampere) per square foot for receptacle loads in commercial spaces. For office buildings, additional receptacles for specialized equipment (like computers or printers) may be required, and their specific wattage should be factored into the calculation.

The NEC allows for a demand factor to be applied to receptacle loads in larger buildings to account for the fact that not all outlets will be used simultaneously. For example, in commercial buildings with a connected load of more than 10 kVA, the NEC allows for a 50% reduction in the load calculation for receptacles.

Step 3: HVAC Load Calculations

HVAC systems are a significant part of the commercial electrical load and must be carefully calculated. The nameplate on the HVAC unit provides the electrical ratings in terms of power input (in kW or amps). You must ensure that the system has enough capacity to handle these loads, especially during peak demand periods such as during the hottest or coldest months.

For HVAC loads, the NEC requires that you size the circuit and overcurrent protection device (e.g., circuit breaker) for 125% of the continuous load plus 100% of the non-continuous load.

Step 4: Calculate Motor Loads

Motors are another significant load in commercial buildings, especially in industrial or manufacturing settings. Motor loads are calculated based on the horsepower (HP) rating of the motor. The NEC provides tables that specify the amperage for different horsepower ratings and voltages.

Motor circuits also require special consideration for overcurrent protection and conductor sizing, as motors typically draw more current during startup than during normal operation. This starting current, also known as inrush current, can be several times higher than the running current.

For motors that run continuously, the circuit must be sized for 125% of the full-load current, per NEC guidelines.

Step 5: Sum the Loads

After calculating the individual loads for lighting, receptacles, HVAC, and motors, the next step is to sum these loads to determine the total connected load of the building.

The total connected load is then used to determine the required capacity of the service entrance and distribution equipment, such as panelboards, transformers, and feeders. The service entrance equipment must be rated to handle the maximum demand load, which is often lower than the total connected load due to diversity factors.

Step 6: Apply Demand Factors and Diversity Factors

The NEC provides guidelines for applying demand factors and diversity factors to reduce the total load calculation. These factors recognize that not all equipment will be operating at full capacity simultaneously.

For instance, the NEC allows for a reduction in the calculated load for lighting, HVAC, and motors based on the building’s usage patterns. By applying these demand factors, the electrical system can be sized more efficiently without compromising safety or performance.

Step 7: Size the Electrical Service

The final step is to size the electrical service, which involves determining the size of the main service conductors, circuit breakers, and other protective devices. This is based on the calculated demand load and must adhere to NEC requirements for conductor sizing and protection.

  • Main Service Conductors: These conductors must be sized to handle the maximum calculated load, with an additional margin for future expansion. The NEC provides ampacity tables that specify the minimum conductor size based on the load and the type of insulation used.
  • Overcurrent Protection: Circuit breakers or fuses must be sized to protect the conductors and equipment from overcurrent conditions. This involves selecting the correct rating for the main service breaker and any subpanels.

Example: Detailed Commercial Electrical Load Calculation for an Office Building

Let’s walk through a detailed example to calculate the commercial electrical load for a 10,000 square foot, two-story office building. This building includes lighting, HVAC systems, receptacles, and some motor-driven equipment, such as elevators and air-handling units.

Step 1: Gather Information on Electrical Loads

Lighting Load:

  • Area: 10,000 square feet.
  • Lighting load based on the NEC (1.3 watts per square foot for an office):
  • 10,000sq ft×1.3W/sq ft=13,000W=13kW

Receptacle Load:

  • Per NEC, the receptacle load is calculated at 1 VA per square foot for general office space:10,000sq ft×1VA/sq ft=10,000VA=10kVA

HVAC Load:

  • The HVAC system consists of two units with a total cooling capacity of 20 tons (1 ton = 12,000 BTU/h).
  • Power requirement per unit: 8 kW (based on manufacturer specs).

Thus, total HVAC load:
2units×8kW=16kW

Motor Load (Elevator):

  • The building has a 10 HP motor for the elevator.
  • From NEC Table 430.250, the full-load current (FLA) for a 10 HP motor operating at 230V, 3-phase, is 28 amps.

Motor load:
28A×230V×3×0.8(Power Factor)=8.9kW

Step 2: Apply Load Factors and Demand Factors

Lighting Load:

  • As per NEC guidelines, lighting in commercial buildings must be calculated at 125% of the continuous load.

Total adjusted lighting load:
13kW×1.25=16.25kW

Receptacle Load:

  • The NEC allows for a demand factor of 50% for receptacles over 10 kVA.

Adjusted receptacle load:
10kVA10kVA×0.50=5kVA

HVAC Load:

  • HVAC systems typically operate as continuous loads, so they must be sized at 125% of their rated load.

Adjusted HVAC load:
16kW×1.25=20kW

Motor Load (Elevator):

  • For motors, the NEC requires the circuit to be sized at 125% of the full-load current for continuous operation.

Adjusted motor load:
8.9kW×1.25=11.13kW

Step 3: Sum the Loads

Now, we sum all the individual loads to determine the total connected load for the building:

  • Adjusted lighting load: 16.25 kW.
  • Adjusted receptacle load: 5 kVA.
  • Adjusted HVAC load: 20 kW.
  • Adjusted motor load (elevator): 11.13 kW.

Total connected load:
16.25+5+20+11.13=52.38kW

Step 4: Apply Diversity and Demand Factors for the Total Load

Let’s apply the diversity factor based on the NEC to account for the non-simultaneous operation of all loads. In office buildings, a diversity factor of 0.80 is commonly used:

Adjusted total load with diversity factor:
52.38kW×0.80=41.9kW

Step 5: Size the Service Equipment

Sizing the Main Service Conductors:

  • The main service conductors must be sized to handle the total load of 41.9 kW.
  • Assuming a 3-phase system at 480V, we calculate the total amperage required.

Total amperage:
I=P3×V×Power Factor=41,9003×480×0.9=56.1A

Thus, the main service conductors should be sized to handle at least 56.1 amps.

Overcurrent Protection:

  • The main circuit breaker must be sized to handle the peak load of 41.9 kW, which corresponds to 56.1 amps. A 60-amp circuit breaker would be a suitable choice.

Sizing Conductors for HVAC and Motors:

  • For HVAC units:

I=20,000W480V×3×0.9=26.9A 

A 30-amp circuit breaker with corresponding conductors should be chosen.
 

  • For motors:

 I=11,130W480V×3×0.9=14.9

A 20-amp breaker and appropriately sized conductors should be used.

Conclusion

This example illustrates the process of performing a commercial electrical load calculation. We calculated the connected loads for lighting, receptacles, HVAC, and motors, applied appropriate demand factors, and sized the electrical service equipment accordingly. By following these detailed steps and applying the principles of load calculation, diversity, and demand factors, you can accurately size the electrical system for a commercial building. This process ensures that the building's electrical infrastructure is safe, compliant with NEC guidelines, and capable of handling present and future demands.

Prasun Barua is an Engineer (Electrical & Electronic) and Member of the European Energy Centre (EEC). His first published book Green Planet is all about green technologies and science. His other …

Post a Comment

© Prasun Barua . All rights reserved. Developed by Jago Desain